The overvoltage mechanism
When the inverter injects power, current flows toward the grid and passes through the impedance of the cable and the transformer. That current raises the voltage at the inverter relative to the voltage at the point of connection. The weaker the grid, that is, the higher its impedance, or the longer the conductors, the greater the rise. When the voltage reaches the protection threshold, the inverter stops and reconnects after a time.
What is observed
Disconnections occur during hours of high production, around midday, when injection is at its maximum and local demand is low. The log shows voltage rising with power and a disconnection on reaching the limit. If a grid voltage sag occurs, an undervoltage trip is a normal protective response.
Usual causes
- High impedance between the inverter and the point of connection, due to long or undersized conductors.
- A weak distribution grid or several installations injecting at once on the same feeder.
- High grid voltage even without generation, due to the regulation of the distribution transformer.
- Protection parameters set more strictly than required.
- A poor connection or high-resistance contact, which adds a local voltage drop.
What to check first
Measure the voltage at the inverter terminals and at the point of connection, comparing both with the injected power. If the difference is large, the cause lies in the wiring or the connection. If the grid voltage is high in itself, the problem is external. Also check the protection settings against what local regulations require.
Possible remedies
Reduce the drop on the AC side with suitable conductors, improve connections and, if the equipment allows it and regulations permit it, use voltage-dependent reactive power control or limit the injected power. Changes to protections must be made by authorized persons, because they are part of grid compliance.