What happens inside the motor
A three-phase motor produces a rotating magnetic field thanks to three phase-shifted currents. If one phase is interrupted, the field is no longer purely rotating: it breaks down into a part that rotates in the normal direction and another that rotates in the opposite direction. This second part is the negative-sequence component.
Why it burns out
- Overcurrent: if the motor was running under load, it must keep delivering the same torque with fewer effective windings, so the currents in the healthy phases rise considerably.
- Rotor heating: the reverse field induces currents of almost double frequency in the rotor, which concentrate at the surface and heat it quickly.
- Less effective ventilation: the loss of torque reduces speed and self-cooling.
- Impossible start: if the motor was stopped, it does not start; it only hums and draws high current that heats it within seconds.
Insulation ages with temperature, and a condition like this takes it past its thermal limit in a short time.
Where the phase loss comes from
An open fuse, a worn contactor contact, a loose connection or an opening upstream. It can also originate on the primary side of a transformer: in certain connections, the loss of a primary phase is reflected on the secondary as unbalanced voltages, which can make it look as if the problem is in the motor.
What the engineer sees
A motor with abnormal noise and vibration, unequal currents in the three phases, heating and tripping of the thermal relay, or else a burned-out motor whose windings show a localized damage pattern. The distribution of the damage depends on the motor connection and helps reconstruct what happened.
How it is prevented
The protection must detect the problem before damage occurs: overload relays sensitive to phase loss and imbalance, phase failure relays and voltage monitoring. Thermal protection without sensitivity to imbalance can take too long.
Before re-energizing, the cause of the phase loss must be found and the other elements of the circuit checked. This work is done by qualified personnel.