What changes during maintenance
A fan is sensitive to balance because its rotor is large and turns at a moderate speed with an unevenly distributed mass. Any intervention can change something: removing deposits, welding a blade, replacing a bearing, reinstalling the coupling or retightening the base.
Most frequent causes
- Unbalance: deposits removed unevenly, a lost balance weight or a repaired blade.
- Impeller mounting: a poorly seated bushing or key produces eccentricity.
- Misalignment: with the motor or with the belt or coupling drive.
- Looseness and base: bolts without the correct tightening or badly placed shims.
- Poorly installed new bearing: incorrect fit, preload or unsuitable lubrication.
- Resonance: a change in stiffness or mass can bring a natural frequency closer to running speed.
How it is diagnosed
- Measure the velocity spectrum, radial and axial, and compare it with the baseline from before the maintenance.
- A dominant peak at one times running speed, with stable phase, points to unbalance.
- A significant axial component suggests misalignment.
- Multiple harmonics indicate looseness.
- Check for resonance with a startup and a shutdown.
What to check first
Before balancing, confirm cleanliness, base tightening and impeller mounting; balancing a poorly mounted rotor only hides the problem. If the unbalance is confirmed, field balancing with phase measurement is usually the next step.
When it is not unbalance
A once-per-revolution peak is not always unbalance: a bent shaft, a loose impeller or a resonance also produce it. If the amplitude does not improve with balancing, or the phase changes with speed, those alternatives must be checked before adding more balance weights.