What Is Dissolved Gas Analysis?

Dissolved gas analysis (DGA) measures the gases generated when thermal or electrical faults or cellulose degradation decompose the insulating oil, and it makes it possible to detect internal transformer problems without opening the unit.

Principle

When oil or paper is subjected to very high temperatures or electrical discharges, its molecules break down and form gases that remain dissolved in the liquid. Each type of fault produces a characteristic mixture. Extracting these gases from a sample and quantifying them by chromatography makes it possible to infer what is happening inside the equipment.

Gases measured

  • Hydrogen: appears in almost all fault types; it stands out in partial discharges.
  • Methane, ethane, ethylene: hydrocarbons associated with thermal faults, at progressively higher temperatures.
  • Acetylene: typical of arcing and very high temperatures.
  • Carbon monoxide and carbon dioxide: linked to cellulose degradation.
  • Oxygen and nitrogen: atmospheric gases that give information about the sealing of the equipment.

What an engineer sees in practice

The report presents the concentration of each gas, sometimes a total of combustible gases and, at many laboratories, an indication of the probable fault type. What matters is the comparison with previous samples from the same transformer: a gas that grows in a sustained or accelerating way is more worrying than a high but stable value.

How it is interpreted

  1. Verify that the sample was taken and transported without contamination or gas loss.
  2. Compare concentrations with the history and with the criteria of the applicable standard.
  3. Evaluate the generation rate of each gas.
  4. Apply a diagnostic method, such as gas ratios or the Duval triangle, only if significant quantities are present.
  5. Decide on actions: resample more frequently, inspect, reduce load or intervene.

Limitations

DGA indicates the presence and probable nature of a fault, but not its exact location. Some gases can come from causes unrelated to a fault, such as certain manufacturing processes, heaters or previous repairs. That is why it is combined with other electrical tests and with the operating history.