What it is
Mineral oils can contain traces of sulfur compounds. Some are harmless or even beneficial as natural antioxidants, but others, such as certain disulfides, are reactive and, at temperature and with copper available, attack the metal. This group of active species is called corrosive sulfur.
Failure mechanism
The compound reacts with the surface of the copper conductor and forms copper sulfide. This dissolves or detaches in colloidal form and migrates into the insulating paper between the winding layers. Copper sulfide is a semiconductor: when deposited in the paper it reduces the paper’s insulating capability and can create conductive paths between turns, leading to internal failures that conventional tests do not always anticipate.
What an engineer sees in practice
- Gray or leaden discoloration of the paper and conductors when the winding is inspected.
- Dissolved gases that suggest local overheating or discharges with no evident cause.
- Failures in equipment with oils that had passed the normal quality tests.
How it is detected
Corrosion tests are used on a copper strip immersed in hot oil, with evaluation of the color change, along with more sensitive methods that include insulating paper. The presence of the suspect sulfur species can also be determined analytically. Each test has a different scope, so it is advisable to choose the one that fits the question: new or in-service oil.
How it is controlled
- Addition of a metal passivator that forms a protective layer on the copper.
- Regeneration or replacement of the oil.
- Limiting the operating temperature and the oxygen supply.
These decisions depend on the diagnosis of the specific equipment and must be evaluated by specialists with the transformer de-energized.