Direct answer
It is an assembly of pump, filters, and accessories mounted on a cart or trailer that connects to the transformer, storage tank, or container to treat the oil in a closed circuit. Depending on its configuration, treatment covers particles only or also water and gases.
Common components
- Transfer pump and hoses with sealed connections.
- Particle filters in coarse and fine stages, with a differential pressure gauge to detect saturation.
- Oil heater with temperature control.
- Vacuum chamber with vacuum pump and condenser (in dehydration and degassing units).
- Sensors and protective devices: level, temperature, pressure, and emergency stop.
Two classes of treatment
Simple filtration removes particles and some free water, and is sufficient for cleaning. Vacuum treatment adds dehydration and degassing, which are essential for filling or topping up transformers and for lowering moisture.
What an engineer sees in practice
The differential pressure across the filters rises as they saturate, and the cartridges are then changed. The volume is recirculated several times, and water, particles, and dielectric strength are verified. A connection with an air leak causes bubbles and loss of efficiency.
What it does not do
It does not remove acids or dissolved sludge, nor does it restore oxidized oil; reclamation exists for that purpose. Nor does it dry the transformer paper on its own.
What to check first when selecting or using one
- Which contaminant has to be removed.
- Flow capacity relative to the equipment volume.
- Cleanliness of hoses and connections before use.
- Compatibility with the type of oil.
Connection to and operation with transformers must be carried out by qualified personnel, with the equipment de-energized.