Operating principle
A coil in the probe tip is driven by a high-frequency signal and generates an alternating magnetic field. If there is a conductive material nearby, that field induces circulating currents in it, called eddy or Foucault currents, which in turn create an opposing field. The effect on the coil depends on the distance, so the conditioner converts it into a proportional voltage within a linear range.
Components
- The probe with its coil.
- An extension cable of compatible length.
- An oscillator or demodulator that drives the probe and delivers the signal.
All three must be matched to each other; changing one alters the sensitivity.
Where it is used
It is the standard sensor for measuring relative vibration and shaft position in machines with fluid-film bearings, and for measuring axial position and rotational speed with a reference mark. It responds from zero frequency, so it also records static position.
What affects the measurement
- Target material: sensitivity depends on the conductivity and permeability of the shaft.
- Target size: it must be larger than the probe footprint.
- Surface finish: marks, magnetization and inhomogeneities produce false signals.
- Environment: other magnetic fields and nearby metal objects can alter the reading.
When it does not apply
It does not measure non-metallic surfaces. For vibration of casings or structures where there is no accessible shaft, an accelerometer is preferred. Its measuring range is short, so it is not suitable for large displacements.
What to check first
If the reading seems unstable, check the initial gap, the tightness of the connectors, the condition of the cable and that the probe-cable-conditioner system is the matched set. Then measure at low speed to evaluate the shaft runout, which is the most frequent cause of false signals.