Concept
Furan is an organic molecule whose five-atom ring contains four carbon atoms and one oxygen atom. Furanic compounds are derivatives of that ring. In transformer diagnostics, the interest lies not in pure furan but in its derivatives, which are generated when cellulose degrades.
Why they appear
Paper and pressboard are made of cellulose, which consists of chains of glucose units. When these chains are broken by heat, water or acids, the released sugar units are transformed into furanic compounds that dissolve in the oil. They are specific to cellulose: mineral oil does not produce them on its own, so their presence points to the solid insulation.
Compounds reported
- 2-furfural (2-FAL), the most abundant and the most widely used.
- 5-hydroxymethyl-2-furfural, associated with oxidative processes.
- 2-furfuryl alcohol, linked to moisture and certain types of paper.
- 2-acetylfuran and 5-methyl-2-furfural, related to high temperatures.
The profile among them offers clues to the mechanism: general degradation, localized overheating or moisture.
How they are analyzed
They are extracted from the oil, then separated and quantified by liquid chromatography. This is a specific analysis, distinct from physical tests and dissolved gas analysis.
How to interpret the result
- The trend is worth more than a single figure.
- Oil that has been filtered, regenerated or replaced loses its fingerprint; without that context, the reading is misleading.
- Thermally upgraded paper generates fewer furans for the same damage, so the same figure does not mean the same condition in two units with different papers.
- The result is an average for the whole unit and can conceal a small hot spot.
- It is complemented by gases (CO and CO2), moisture and loading history.
This body of evidence is used to judge the condition of the solid insulation, which is the factor that most limits the life of a transformer, since the oil can be treated or replaced and the paper cannot.