Main functions
Oil is not a mere filler. In an immersed transformer it performs at least four functions that support one another.
1. Electrical insulation
It has a high dielectric strength and, together with the paper and pressboard, forms a composite insulation system. The liquid occupies the spaces between windings, core and tank, where air would insulate less well and would allow discharges at much greater distances.
2. Cooling
Copper and core losses are converted into heat. The oil absorbs it, circulates by natural or forced convection, and releases it to the outside through radiators or heat exchangers. If its viscosity rises or sludge forms, cooling worsens and the winding temperature increases.
3. Impregnation of the cellulose
Dry paper and pressboard have pores full of air. By impregnating them, the oil eliminates the voids where partial discharges would occur and improves the dielectric strength of the assembly. That is why filling is done with the equipment dry and under vacuum.
4. Arc quenching and diagnostics
In tap changers and other oil-immersed devices, the liquid helps extinguish switching arcs. In addition, because electrical and thermal faults degrade the oil and generate dissolved gases and compounds, periodic analysis reveals what is happening inside without opening the equipment.
What an engineer sees in practice
The parameters tracked in the oil are dielectric strength, water content, acidity, interfacial tension, color, dissolved gases and particles. Changes in these point to moisture, oxidation, contamination or incipient faults.
When there is a risk
Oil is combustible and the equipment operates at high voltage. Sampling, filling and any intervention must be carried out by qualified personnel, applying the corresponding electrical safety regulations.