Central idea
A hermetically sealed transformer is filled, sealed and does not breathe. In conservator designs, the oil expands into an upper tank that communicates with the atmosphere through a desiccant; in the hermetically sealed design, that exchange does not exist.
How expansion is absorbed
- Tank with corrugated walls or flexible radiators: the walls deform elastically as the oil heats up.
- Diaphragm or bladder in the conservator: a membrane separates the oil from the outside air.
- Inert gas cushion: a nitrogen chamber above the oil absorbs volume changes. This is a conceptual variant that some distinguish from strictly hermetic sealing.
What is gained
Oxygen and moisture from the air are the main promoters of oil and paper aging. Preventing them from entering simplifies maintenance, since there is no desiccant to replace, and the oil stays in better condition for longer.
What it requires
- Internal pressure varies with temperature, so relief valves and sometimes pressure and level indicators are fitted.
- A leak lets moisture in unnoticed, and the loss of sealing is detected late.
- Sampling must avoid introducing air; dissolved gases are retained in the unit, which makes diagnosis easier.
- Internal repair or inspection is not possible without breaking the seal and restoring it afterward.
What an engineer sees in practice
Nameplates that state the hermetically sealed construction, no breather, and a compound pressure-vacuum gauge or level indicator. Bulging or a drop in level are signs that call for a check.
Work on the seal or on tank pressure must be carried out by qualified personnel following the manufacturer’s instructions and applicable regulations.