General scope
ASTM D495 deals with the arc resistance of solid insulating materials subjected to a high-voltage, low-current electric arc under dry conditions. It is a comparative test that ranks materials by the time they resist until the arc stops extinguishing or the material becomes conductive.
How it is set up
Two electrodes rest on the surface of the specimen and an arc is generated between them. The severity of the test is increased in stages: the current and the duration of the arc periods are raised according to a defined sequence. The total time until the surface fails is recorded, whether through formation of a conductive path, ignition or melting. The result is expressed as a time, which is then associated with a classification of the material.
What mechanisms it tests
- The ability of the material not to form conductive carbon under the heat of the arc.
- The thermal stability of the surface and its erosion.
- The tendency to emit gases and to melt.
Inorganic materials or those with fillers that leave no carbon usually perform better, and polymers that carbonize easily perform worse.
Differences from other tests
It is not a tracking test: tracking tests are carried out with wet contamination and at mains voltages. Nor does it reproduce high-current arcs, such as those from short circuits, which cause damage through erosion and pressure. For that reason its result is a guide, but it does not replace arc tests appropriate to the application.
How to interpret the result
- Use the value to compare materials tested with the same method.
- Take into account formulation, color and fillers, which change the result.
- Check the current edition of the standard before specifying the acceptance criterion.
Safety
The test involves high voltage and the emission of fumes. It must be carried out by qualified personnel, with ventilation and safety measures in accordance with the applicable regulations.