What Does a Variable Frequency Drive Do?

A variable frequency drive controls the speed and torque of an AC motor, generating a voltage of adjustable amplitude and frequency from the supply by means of a rectifier, a DC bus and an inverter.

What it does

The speed of an induction or synchronous motor depends on the supply frequency and the number of poles. The drive produces a supply with adjustable frequency and voltage, and thereby makes it possible to control the speed, acceleration and torque of the motor.

How it is built

  1. Rectifier: converts the AC voltage of the supply into DC.
  2. DC bus: capacitors, and sometimes an inductor, that store energy and smooth the voltage.
  3. Inverter: power transistors, normally IGBTs, that switch rapidly to synthesize the output through pulse width modulation. The motor receives a pulsed voltage whose average effect, because of the motor’s inductance, is a nearly sinusoidal current.
  4. Control: in the simplest mode it keeps the voltage-to-frequency ratio proportional to maintain the magnetic flux; vector modes control flux and torque separately.

What it offers

  • Soft starting with controlled current.
  • Speed matched to the process. In pumps and fans, the power required drops very sharply as speed decreases, because of the affinity laws, so the energy savings can be large compared with throttling with a valve or a damper.
  • Torque and acceleration control, and motor protection functions.

What side effects must be considered

  • On the supply: the rectifier produces harmonic currents.
  • On the motor: pulses with a high rate of voltage change, especially with long cables, place more stress on the insulation and can generate bearing currents.
  • Cooling: a self-ventilated motor cools less at low speed.
  • Braking: stopping high-inertia loads requires dissipating the energy in a resistor or returning it to the supply with regenerative equipment.

How it is chosen

It is selected according to the type of load (variable torque or constant torque), the motor current and the application. Work on the drive, whose bus retains charge after disconnection, must be done by qualified personnel.