24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How is the distortion a charger generates on the grid measured?

The distortion a charger injects into the grid is measured with a power quality analyzer at the AC input, logging current harmonics, total distortion and power factor at different power levels throughout the charging session.

What is being sought

A charger contains a rectifier and, in most designs, a power factor correction stage. Its input current may contain components at multiples of the grid frequency. This harmonic current, passing through the grid impedance, distorts the voltage seen by other users. Measuring the charger consists of quantifying those currents and comparing them with the criterion of the applicable emissions standard.

How it is measured

  1. A power quality analyzer is connected at the charger supply, with voltage and current sensors on each phase.
  2. The instrument is configured to calculate individual current harmonics and total distortion, with a time aggregation that complies with the method in the standard.
  3. Measurement covers a complete session, not just a few seconds.

Why a single reading is misleading

Harmonic current depends on the power the charger is delivering. At the start of the session the power is high and, as the battery approaches full charge, the current falls. At low power the relative harmonic content tends to increase, even if the absolute value is small. Measuring at only one point can miss the worst case. It is advisable to log at several power levels and also with the charger on standby.

Quantities to distinguish

  • Current distortion: a property of the charger.
  • Voltage distortion: also depends on the grid impedance and other loads; a flawless charger can show distorted voltage if the source is weak or if distortion already existed.
  • Power factor: combines phase shift and distortion; a charger can have zero phase shift and still a power factor below one because of distortion.

How to interpret the result

To find out whether the charger is the cause of a problem, the harmonic voltage is compared with the charger off and on, and measured at the point of common coupling. Assessing compliance requires the test conditions of the current standard. Connections in energized panels must be made by qualified people in accordance with the applicable electrical safety regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer