How Do You Correct Insulation Resistance for Temperature?

Insulation resistance falls as temperature rises, so it is corrected by multiplying the reading by a coefficient that brings it to a common reference temperature.

Why correction is needed

In insulating materials, heat makes ion movement and conduction easier. Resistance therefore decreases as temperature rises, and it does so approximately exponentially, not linearly. Two readings of the same equipment, one cold and one hot, can differ greatly without any change in the insulation. To compare with the history or with an acceptance criterion, they must be expressed at the same temperature.

How it is done

  1. Measure the insulation temperature, not the ambient temperature. In a motor, it is approximated by the winding or frame temperature after stabilization; in a transformer, by the oil or winding temperature as appropriate.
  2. Choose the reference temperature used by the applicable criterion or standard; use the one specified by the adopted procedure and always keep it the same.
  3. Obtain the correction coefficient for that temperature difference. It is taken from tables or curves in the standard, from the manufacturer or from the equipment’s own data.
  4. Multiply the reading by the coefficient. If the equipment is hotter than the reference, the coefficient is greater than one and the corrected resistance is higher than the measured value.

Limitations worth knowing

  • The coefficient depends on the type of insulation and its condition: a generic table is an approximation.
  • If the insulation is wet or contaminated, its behavior with temperature differs from that of clean, dry insulation.
  • Measuring while the temperature is still changing introduces error.
  • The correction does not apply to the polarization index, which is a ratio between two readings taken in the same test and at almost the same temperature.

What the engineer sees in practice

A motor measured after running can give a much lower resistance than when started cold. After correction, both readings should be similar; if they are still very different, the cause is not only thermal and moisture or contamination should be checked.

These activities involve hazardous voltages: they must be performed by qualified, authorized personnel, following applicable regulations and the facility’s lockout and grounding procedures.