What really needs to be measured
What matters to a server is the temperature of the air entering at its front, because that is the air that cools its components. The reading from the air conditioning thermostat, sometimes located in the return, does not represent that condition. For this reason, monitoring is organized around the air intake of the racks.
Where to place the sensors
- At the front of the racks, at different heights: the top is usually the hottest because of recirculation.
- At the ends of rows, where hot air can wrap around the rack.
- At the supply and return of the cooling system, to determine the air temperature difference.
- Near areas of high load density.
What is logged
Temperature and relative humidity, since air that is too dry promotes electrostatic discharge and air that is too humid promotes condensation and corrosion. The presence of water on the floor and the status of the climate control equipment can also be logged. Allowable ranges are set by the equipment manufacturer’s recommendations and industry guidelines, and they must be taken from those sources.
Alarms and trends
A single high threshold is slow to give warning. It is better to define warning and alarm levels and to watch the rate of change: a rapid increase indicates a cooling failure even if the absolute temperature is still acceptable. An occasional thermal camera survey helps to find hot spots, although it does not replace continuous logging.
What the engineer sees
The data often show that two racks with the same load have very different temperatures because of air distribution. The usual causes are open gaps without blanking panels in the racks, mixing of hot and cold air, cables obstructing the flow, or badly placed floor tiles.
Maintaining the measurement
Sensors drift, so they are periodically compared with a standard or calibrated, especially humidity sensors, which tend to be the least stable.