Principle
A soft starter uses pairs of thyristors connected in antiparallel in each phase, between the supply and the motor. A thyristor conducts only after receiving a firing pulse, and the instant of the pulse within each half-cycle determines what fraction of the wave reaches the motor. With delayed firing, the RMS voltage applied to the motor is low; as the firing is advanced, the voltage rises to the full value.
Why it reduces current and torque
Motor current is approximately proportional to the applied voltage. The torque of an induction motor is approximately proportional to the square of the voltage. Starting at reduced voltage lowers the starting current and the mechanical shock on the coupling and the load. The price is that available torque falls faster than current.
What can be configured
- Voltage or torque ramp: the time in which the voltage rises from an initial value to full voltage.
- Current limit: keeps the current below a ceiling during the start.
- Kick start: an initial pulse to overcome high-friction loads.
- Soft stop: a downward ramp, useful in pumps to soften water hammer.
The bypass contactor
Once the ramp is complete, many starters close a contactor in parallel with the thyristors. This avoids heat dissipation in the semiconductors during normal operation and improves efficiency, while the unit retains its protection functions.
When it does not apply
It does not regulate speed: it only manages the initial acceleration. A load that demands high starting torque may fail to accelerate at reduced voltage. During the ramp the motor receives a waveform with harmonics, and with frequent starts the thyristors heat up, so the manufacturer’s duty cycle must be respected. If speed control is required during operation, the right equipment is a variable frequency drive.
What the engineer sees
In a recording, the starting current rises smoothly and stays limited, unlike the peak of a direct-on-line start. Work on the starter and the motor is for qualified personnel.