Hot Collar Testing with Power Factor Tan Delta

A test that measures the condition of bushing insulation between the sheds and the conductor. It is intended for those responsible for maintaining transformers and high-voltage equipment.

Hot collar testing with power factor tan delta on a bushing

What the test measures

It measures the condition of a section of the bushing insulation, between the surface of the sheds and the conductor. It is performed by energizing one or more collars placed around the bushing porcelain and grounding the center conductor (terminal). It is useful for detecting cracks in the porcelain or a low level of liquid or compound.

What it helps detect

  • Internal moisture contamination in the upper area of compound-filled bushings.
  • Cracks and fractures in the porcelain.
  • Low compound or liquid level.

The test reflects the condition of the insulation in the upper part of the bushing. If high loss values are obtained, it is recommended to repeat the test on each shed to analyze the magnitude of the fault.

Multiple collar test

It gives information on the general condition of the insulation between the flange and the center conductor.