DC or Very Low Frequency Testing on Cables?

For extruded medium-voltage cables, very low frequency is usually preferred over direct current, because it distributes the field as in service and avoids the space charge that DC leaves in the insulation.

The underlying difference

With alternating current, the electric field is distributed in the insulation according to its permittivity. With DC, after a transient period, it is distributed according to resistivity, which depends heavily on the temperature and condition of the material. For this reason a DC test does not reproduce the stress the cable experiences in service.

What happens with DC in extruded insulation

In polymers such as cross-linked polyethylene, DC can build up space charge: trapped charges that alter the local field. When the cable is re-energized with AC, this charge can intensify the field and promote failures shortly after the test, especially in aged cables. DC also detects certain defects poorly, such as water trees, which can pass the test and fail later.

What very low frequency offers

  • It is an AC voltage at a frequency much lower than that of the grid, so the field is distributed in a way similar to service.
  • Capacitive current is proportional to frequency, so the equipment needed is much smaller than would be required at grid frequency.
  • It is compatible with withstand tests and with diagnostics such as dissipation factor and partial discharge.

When each one is justified

  • DC: historically used on impregnated paper cables and in simple acceptance tests where the applicable criterion allows it. It is simple and lightweight.
  • Very low frequency: preferred for cables with extruded insulation and for diagnostics.

How to decide

The choice depends on the type of insulation, the age of the cable, the purpose of the test and what the applicable standard or specification prescribes. When in doubt with extruded cable, high-level DC is avoided.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.