What can fail in a winding
A winding can open, short between turns, lose insulation to the core or frame, or become unbalanced with respect to the other phases. Each defect requires a different test, because no single test detects everything.
Basic tests
- Winding continuity and resistance: an infinite value indicates an open circuit. In a three-phase motor, the three phases must have very similar resistances; a noticeable difference suggests a faulty connection or shorted turns.
- Insulation resistance to ground: this is measured with a high-voltage DC instrument, the megohmmeter. A low value indicates moisture, contamination or insulation deterioration.
- Polarization index and trend: comparing readings taken at different times helps distinguish surface moisture from deeper deterioration.
- Turn-to-turn test (impulse or surge): applies voltage pulses and compares the response of each phase; it reveals turn-to-turn shorts that resistance does not detect, because a single shorted turn barely changes the total resistance.
How to do it in order
- De-energize, lock out and verify the absence of voltage.
- Disconnect the winding from the rest of the circuit and from the drive, if there is one.
- Measure the resistance of each phase and compare the phases with each other and with previous data.
- Measure insulation to ground and record the temperature, because insulation varies with it.
- If shorted turns are suspected, apply a specific comparative test.
How to interpret the result
A single reading is worth little; the trend over time and the comparison between phases tell you more. Acceptable insulation does not rule out a turn-to-turn short, and neither does balanced resistance. Insulation tests apply high voltages and can damage an already weakened winding if done without judgment.
This work involves electrical risk; it must be carried out by qualified personnel in accordance with applicable regulations.