The underlying difference
The distinction is one of time scale and of what is measured. A temporary overvoltage is a rise in RMS value: the wave remains sinusoidal, but with greater amplitude for several cycles, seconds or longer. A transient is a fast phenomenon superimposed on the wave, an impulse or damped oscillation lasting from microseconds to a few milliseconds, which shows up in the waveform, not in the RMS value.
What produces them
Temporary overvoltage:
- A ground fault in a system with an isolated or high-impedance neutral, which raises the voltage on the healthy phases.
- Sudden load loss in a generator-fed system.
- Ferroresonance between a transformer’s inductance and a capacitance.
- Inadequate regulation, for example poorly chosen transformer taps.
Transient:
- Lightning strikes nearby or on lines.
- Circuit breaker switching, especially of capacitor banks or inductive loads.
- Power electronics commutation.
Why the distinction matters
The effects are different. A temporary overvoltage produces heating and saturation in transformers, sustained stress on insulation and tripping of overvoltage protection. A transient produces instantaneous dielectric stress, insulation puncture, semiconductor damage and spurious electronic trips, and it is countered with surge suppressors and good grounding and equipotential bonding practices, not with voltage regulators.
What an engineer sees in practice
A recorder that averages RMS values will clearly show a temporary overvoltage but may miss a transient completely. Transients require waveform capture with a high sampling rate and a trigger on peak or abrupt change. If equipment fails while the RMS record shows nothing abnormal, suspicion falls on transients.
How to decide which to suspect
If the RMS voltage rises and stays up, think of regulation, disconnected loads or ground faults. If sudden damage to electronics or insulation coincides with storms or switching operations, think of transients. The exact boundary between the two depends on the classification standard used.