Why Do Nonlinear Loads Distort the Waveform?

A nonlinear load distorts the waveform because its current is not proportional to the applied voltage: it draws current during only part of the cycle, and that non-sinusoidal current breaks down into harmonics of the fundamental frequency.

The physical answer

An ideal resistor draws a current proportional to the voltage, with the same shape. A nonlinear load does not: its effective impedance changes during the cycle. A rectifier with a filter capacitor, typical of switch-mode power supplies, conducts only when the line voltage exceeds the capacitor voltage, that is, near the peaks. The resulting current is a series of narrow pulses rather than a sine wave.

From waveform to harmonics

Any periodic wave can be broken down into a sum of sine waves: the fundamental and integer multiples of its frequency, which are the harmonics. The more abrupt the shape of the current, the more harmonic content it has. The symmetry of the wave determines which ones appear. A six-pulse three-phase rectifier mainly generates harmonics of order 6k±1 (fifth, seventh, eleventh, thirteenth), while the single-phase rectifiers in switch-mode power supplies also generate the third-order harmonic and its odd multiples.

Other sources of nonlinearity

  • Variable frequency drives and controlled rectifiers.
  • Arc furnaces and welders, with irregular distortion.
  • Transformers and motors with saturating cores, especially at high voltage.
  • Lighting with electronic ballasts or LEDs.

How current becomes voltage distortion

Harmonic current in itself is a load problem, but it flows through the source impedance (transformer and network). By Ohm’s law, each harmonic current produces a harmonic voltage drop across that impedance, and that distorted voltage is what the other equipment connected at the same point sees. That is why a weak source, with high impedance, amplifies the effect of the same load.

What an engineer sees in practice

On an oscilloscope or analyzer, the current shows peaks instead of a sine wave and the voltage appears flattened at the crests. The current crest factor rises, total harmonic distortion of the current is high, and the RMS value measured with non-true-RMS instruments is incorrect. Indirect symptoms are overheating of transformers, neutrals and capacitors.

How to interpret it

Current distortion characterizes the load; voltage distortion characterizes the interaction between the load and the network. Measuring both at the same point makes it possible to tell who is contributing the distortion.