What happens inside the equipment
A switch-mode power supply rectifies the grid voltage and stores energy in an input capacitor. The electronics run on that energy, which is why they tolerate small dips in the supply. During a sag, the grid stops recharging the capacitor, and the capacitor discharges as it feeds the load. As long as the DC voltage stays above the minimum, the equipment notices nothing. If the sag is too deep or lasts too long, the voltage falls below the threshold, the supply stops regulating and the equipment resets, or its undervoltage supervision causes a shutdown.
What determines whether the equipment rides through
- Depth and duration of the sag, and not the average voltage value.
- Stored energy relative to the power the equipment consumes: heavily loaded equipment uses up its reserve sooner.
- Point in the cycle at which the sag begins, which influences how much energy is lost before the first recharge.
- Protection thresholds: drives, PLCs and power supplies have undervoltage settings.
Other elements that react
Contactors and relays with AC coils can drop out in a deep, brief sag and do not re-energize by themselves when the voltage returns, which stops the process even if the electronics survive. Drives can detect undervoltage on the DC bus and trip.
What an engineer sees in practice
Stoppages or resets that coincide with a recorded RMS drop event. Manufacturers often provide voltage-versus-duration tolerance curves, such as the well-known ITIC curve, which are used to compare recorded events with what the equipment should withstand.
How to improve tolerance
- Increase the energy reserve, with more capacitance or with backup on the DC bus.
- Feed critical controls from a UPS or a battery-backed DC supply.
- Review undervoltage thresholds and times in drives and controllers.
- Use contactors with time delay or ride-through, or feed their coils from DC.
Any work in panels must be done by qualified personnel.