Why Does Insulation Fail from Prolonged Overheating?

Prolonged overheating chemically degrades the insulation, which becomes brittle and loses dielectric strength and mechanical strength, until vibration, an overvoltage or moisture causes the failure.

The relationship between temperature and life

The degradation of insulating materials is a chemical process whose rate grows exponentially with temperature. As a result, a small sustained temperature excess greatly shortens service life, while operating below the limit extends it. Aging is cumulative: the effect of each hot period adds up.

What happens inside the material

  • Molecules break or oxidize and the material loses flexibility.
  • Varnishes and resins crack, and the insulation separates from the conductor.
  • Cavities and delaminations appear, in which partial discharges start.
  • The cellulose of a transformer depolymerizes and loses mechanical strength, in addition to releasing water and gases.

In the end, the insulation may still hold the voltage at rest, but it gives way under mechanical stress, a start, a nearby short circuit or an overvoltage.

Where the excess heat comes from

  1. Sustained overload.
  2. Poor ventilation or cooling, clogged filters, dirty fins.
  3. Ambient temperature higher than the design temperature.
  4. Harmonics and voltage or current unbalance, which increase losses.
  5. Loose connections that produce hot spots.
  6. Frequent starts in motors.

How it shows up in practice

It appears as darkened or brittle-looking insulation, a burnt smell, a declining insulation resistance trend and, in transformers, dissolved gases associated with thermal degradation. The failure usually takes the form of a shorted turn or a ground fault at the hottest point.

What to check first

Before repairing, identify and correct the cause of the heat; otherwise, the new insulation will go the same way.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.