24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

Why Does Cable Termination Insulation Fail?

Cable termination insulation fails because the termination is the point where the shield is cut and the electric field concentrates, so assembly defects, moisture or contamination can initiate discharges and leakage.

Why the termination is a critical point

In the cable, the semiconducting shield keeps the field radial and uniform. At the termination, when that shield is removed, the field concentrates at the cut edge and a component along the surface also appears. If this is not controlled, the insulation suffers discharges and the surface degrades.

How the field is controlled

The termination incorporates a stress control system, such as a geometric cone or a high-permittivity material, that spreads the field smoothly across the transition zone. If this system is badly positioned, wrongly sized or damaged, the protection is lost and the local field exceeds what the material can withstand.

Main causes of failure

  • Poor assembly: cuts that damage the insulation, remnants of semiconducting shield, a dirty surface or one with fingerprints, voids between layers.
  • Moisture: water entering through defective seals facilitates leakage and conductive paths.
  • External contamination: deposits on the surface of outdoor terminations that cause surface leakage and discharges.
  • Tracking paths: repeated leakage carbonizes the surface and creates a conductive path that advances.
  • Thermal and mechanical stresses: load cycles that loosen the contact or displace the components.
  • Incompatible components or components not suited to the voltage and type of cable.

Common errors

  • Reusing or improvising parts from a different kit.
  • Not following the cutback dimensions specified by the manufacturer.
  • Leaving dust, grease or moisture on surfaces before assembly.
  • Not verifying the grounding of the shield.

What is observed in practice

Before failure, partial discharges or surface leakage are usually detected; after failure, carbonization marks and erosion appear in the transition zone.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer