24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

Why does an induced-voltage shock occur?

An induced-voltage shock occurs because a de-energized conductor that is close to energized lines or equipment, or exposed to a varying field or a lightning strike, acquires voltage through electric or magnetic coupling.

A conductor with no source can still have voltage

A conductor disconnected from every source is not necessarily at zero potential. If it is near other energized conductors or in a varying electromagnetic field, it can acquire voltage with no electrical connection. This is a normal physical phenomenon, not a fault.

Coupling mechanisms

  • Capacitive (electric) coupling: there is a capacitance between the energized conductor and the isolated one. The isolated conductor “floats” and acquires a potential determined by the ratio between that capacitance and the capacitance to ground. If it is touched, the capacitance delivers current through the person.
  • Inductive (magnetic) coupling: the alternating current of a parallel line produces a varying magnetic field that induces a voltage in the conductor, especially when it is long and runs in parallel. If a loop to ground is closed, current will flow.
  • Lightning: a nearby strike induces transient overvoltages in lines and structures, even at a distance.
  • Static charges: these can build up on isolated conductors or on equipment.

What the magnitude depends on

  1. Length of the section parallel to the energized line.
  2. Separation between the two conductors.
  3. Current and voltage of the inducing line.
  4. Condition of the induced section: floating or grounded at some point.

Why it is dangerous

The current is sometimes small, but it can cause a startle reaction, falls from height or, in extreme cases of long, nearby lines, values that are dangerous to the body. It also confuses measurements: a high-impedance instrument can show a high apparent voltage that disappears when the circuit is loaded.

How it is controlled

The usual measure is to temporarily ground the conductor being worked on, at the point or points defined by the procedure, and to create an equipotential work zone, so that the person and the part being worked on are at the same potential. Work on lines is also suspended when there are storms nearby.

These operations are the responsibility of qualified personnel, following the applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer