Parts that can fail
A relay has a coil that generates a magnetic field, a movable spring-loaded armature, and contacts that close or open the circuit. Each of these parts has its own failure mode.
Contacts
The contacts are the most common cause. When they open or close under load, an arc forms that erodes the material and transfers it from one contact to the other. Over time, contact resistance rises because of pitting and films, and the relay heats up or stops conducting well. Two extremes are typical:
- Welded contacts: the closing current, for example with capacitive loads, lamps or motors, locally melts the contacts and they stick together. The relay stays closed even when the coil is de-energized.
- Eroded or contaminated contacts: resistance rises, particularly with low-current loads where the arc does not clean the surface.
Inductive loads, such as coils and motors, generate an overvoltage on opening that prolongs the arc; without a suitable suppression circuit, wear accelerates.
Coil
- Open coil or shorted turns: the relay does not operate, or operates with insufficient force.
- Supply voltage out of range: if it is low, the armature does not close firmly and the contacts chatter; if it is high, the coil overheats.
- Prolonged heating degrades the winding insulation.
Mechanism
Springs lose force, hinges wear, and dust or corrosion can prevent movement. This changes the operating times and the contact pressure.
What an engineer sees in practice
- The click is heard but the load receives no current: worn or oxidized contacts.
- No click: check the voltage at the coil and its continuity.
- The load does not disconnect: welded contacts or a stuck armature.
- The relay squeals or hums: coil voltage insufficient or with high ripple.
How to interpret the result
Measure the coil resistance and compare it with the manufacturer’s data sheet, and measure the voltage drop across the closed contacts under load. A high drop indicates contact degradation even if there is continuity. Electrical life is much shorter than mechanical life, so the relay must be selected according to the type of load and not only by its rated current.