How an arc starts
An arc forms when the air between two conductors at different potentials stops insulating and becomes conductive, ionized by a discharge. From then on it sustains itself as long as voltage and current are available, and it releases a great deal of energy in a very short time.
Common initiating causes
- Accidental contact: a tool that falls or rests across busbars, a loose cable, a screw dropped during work.
- Loose connections: they generate heat, degrade the material and can end in a fault.
- Contamination: conductive dust, moisture and dirt create surface paths across the insulation.
- Insulation deterioration from aging, heat or overvoltages.
- Animals or foreign objects inside the enclosure.
- Switching with deteriorated equipment: a breaker that does not open properly or a worn mechanism.
- Procedural errors: opening or closing under load, removing or inserting drawout components incorrectly, or assuming a circuit is de-energized without checking.
What makes the outcome worse
- Long clearing time: the protection is delayed because of settings chosen for selectivity, poor maintenance or a failure in its tripping.
- High available current.
- Short distance between the worker and the arc location.
- Open doors or missing covers, which let the event escape toward the person.
- Personal protection inadequate for the actual energy.
What can be seen and what prevents it
Precursors include hot spots detected by thermography, a burning smell, discoloration, buzzing or partial discharges. Prevention combines scheduled maintenance, cleaning, tightening of connections, remote operation, panels designed to contain the arc, and the principle of working de-energized whenever possible.
How to interpret the analysis of an event
When investigating an accident, the aim is to find the chain of causes: what started the arc, why the protection was slow, why the person was close, and why the personal protection was inadequate. The root cause usually lies in planning or maintenance, not just in a one-off lapse.
Work on energized panels must be done by qualified personnel, following the applicable regulations.