What the arc in a contactor is
An arc always appears when a current is interrupted, and the contacts, the arc chute and the design itself are built to control it. The problem arises when the arc occurs abnormally, lasts longer or carries more energy. The contact material then erodes, transfers from one contact to the other, and the surface becomes rough and resistive.
Main causes
- Insufficient coil voltage: if the control circuit voltage drops during starting, the contactor closes with little force, the contacts bounce and the arc repeats on every bounce. In extreme cases the contactor chatters between closed and open.
- Faulty electromagnet: dirty or damaged core faces, or a broken shading ring, cause humming, vibration and unstable contact.
- Weakened contact pressure springs: the contact does not press hard enough and contact resistance rises, which in turn causes heating.
- Wrong utilization category: switching off running motors is not the same as interrupting stalled motors or performing reversing or jogging duty, which are much more severe for the contacts.
- Contamination and wear: dust, moisture and accumulated operations.
- Overcurrent: a short circuit can weld the contacts if the protection does not limit it enough.
What the engineer sees
Humming, pitted or blackened contacts, weld spots, overheated terminals and, at the motor, a lost phase or imbalance caused by a contact that does not close properly. A welded contact is especially dangerous because the contactor can no longer disconnect the load.
How to diagnose it
- Measure the coil voltage at the moment of starting, not only at rest.
- Check that the contactor’s utilization category matches the actual duty.
- Inspect the condition and wear of the contacts, without overpolishing or filing them.
- Verify coordination with the short-circuit protection.
- Replace the contacts as a set, not individually.
Tests and inspection are carried out with the circuit de-energized and locked out, by qualified personnel.