24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

Why Do Connection Points in a Panel Heat Up?

A connection heats up because its contact resistance is higher than intended, and the current passing through it generates heat proportional to that resistance and to the square of the current.

The mechanism

The heat generated in a connection is the contact resistance multiplied by the square of the current. In a well-made joint, the effective contact area is large and the resistance is minimal. If the actual contact area shrinks, the current concentrates at a few points, the local resistance increases and the temperature rises.

Why the contact degrades

  • Insufficient tightening from installation or loosening over time.
  • Load cycles that expand and contract the materials; aluminum and some alloys creep under pressure and lose tightness.
  • Oxidation and contamination of the surfaces.
  • Use of dissimilar metals without suitable treatment, which promotes galvanic corrosion.
  • Terminals or lugs unsuited to the gauge or the conductor material.
  • Conductors with broken or poorly prepared strands.

The process feeds on itself: higher temperature oxidizes the joint further, which raises the resistance and drives the temperature up again, until the insulation is damaged or the metal melts.

How it is detected

Infrared thermography with the equipment under load reveals hot spots. Interpretation is done by comparing phases with one another and with similar points, and by taking into account the current at the time of measurement, because a spot that is cold without load can be critical at full load. Ultrasound and visual inspection for discoloration or burned insulation complement the diagnosis.

Common mistakes

  • Performing thermography at low load and concluding that everything is fine.
  • Evaluating only the absolute temperature without comparing against other phases or the current.
  • Tightening by feel instead of applying the torque specified by the manufacturer.
  • Reusing deteriorated hardware or terminals.
  • Correcting the symptom without checking whether the connection is overloaded.

What to check first

Confirm the actual current, the condition of the surfaces and the tightness with the equipment de-energized and locked out. If the connection is damaged, it is replaced and cleaned before closing up again. Opening panels and taking energized measurements present an arc flash hazard, so they are for qualified personnel under the applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer