First, separate the resource from the system
Production depends on how much sun arrived. Before looking for faults, measure the irradiance in the plane of the modules and calculate what the system should have produced with that value and the actual temperature. If production matches the model, the problem lies in the expectation or the resource. If it is lower, there are losses to locate.
Families of losses
- Soiling and shading, which lower the current of modules or strings.
- Temperature: the higher the cell temperature, the lower the voltage and the power.
- Mismatch between modules and strings, due to manufacturing differences, aging or degradation.
- Ohmic losses in DC and AC conductors and connections.
- Inverter conversion efficiency, and clipping when the array power exceeds its capacity.
- Unavailability: stoppages due to faults, protections or maintenance.
- Accumulated module degradation.
How the cause is located
Compare production by inverter and by string. A string with lower current than the others points to damaged modules, shading or connectors. If all the strings perform equally and below expectation, review the resource, widespread soiling, sensor calibration and inverter configuration. The I-V curve of suspect strings and thermography provide additional evidence.
What an engineer sees in the field
Frequently, several small causes add up to the difference rather than one large fault. An out-of-calibration irradiance sensor can create the impression of a problem where there is none, or hide one. That is why the instruments are verified before reaching a conclusion.
How to interpret the trend
A stable loss from the start suggests a design or expectation error. A loss that grows over time points to degradation, soiling or progressive faults. A sudden loss indicates an event, such as a disconnected string or an inverter that has stopped.