Energy, not just current
During a fault, the current returning through the ground conductor produces heat by the Joule effect. The energy released is proportional to the square of the current multiplied by the duration of the fault, that is, to I²t. Because the event is brief, the heat has almost no time to dissipate into the surroundings and accumulates in the conductor itself. That is why it is treated as adiabatic heating: all the energy raises the temperature of the metal.
What the temperature rise depends on
- Fault current. When it doubles, the energy quadruples for the same time.
- Clearing time. It depends on the protection. A faster device limits the energy.
- Cross-section. A larger cross-section means more mass to absorb heat and lower resistance.
- Material. Copper, aluminum and steel differ in resistivity, specific heat and permissible temperature.
The design relationship can be expressed as follows: the required cross-section grows with the current and with the square root of the clearing time, and is divided by a constant specific to the material and to the permitted initial and final temperatures.
What an engineer sees
An undersized conductor can soften, deform or melt. But the most vulnerable point is hardly ever the conductor: it is usually the joint, where contact resistance is higher and heat concentrates. A loose or corroded mechanical connection can open during a fault, just when it needs to conduct.
A qualitative example
Take two conductors of the same material with the same fault current: if one is cleared by instantaneous protection and the other by time-delayed protection, the second receives much more energy and needs a larger cross-section or better-coordinated protection. That is why the calculation starts from real fault current data and device operating times.
What else to consider
Fault current can divide among several paths, so that not all of it flows through a single conductor. Permissible temperatures depend on the type of joint and on nearby insulation. Criteria and constants must be taken from the applicable regulations in force. Measurements and work in energized electrical installations must be done by qualified personnel, following the applicable regulations and the site’s safety procedures.