Why does a DC connector fail?

A DC connector almost always fails because of high contact resistance: a defective crimp, a poorly mated joint, moisture or connectors that are not compatible. That resistance heats up, gets worse over time and can end in an arc.

The failure process

The current produces heat proportional to the contact resistance. If the contact is poor, it heats up, the metal oxidizes or the plastic deforms, the resistance increases and the heating grows. It is a self-reinforcing process that can end in melted plastic, an electric arc and fire.

Why direct current is especially delicate

Alternating current passes through zero dozens of times per second, which helps extinguish an arc. Direct current does not, so a DC arc can be sustained as long as voltage and power are available. And in a module, there is no way to remove the voltage while it is receiving light.

Most frequent causes

  • Crimping with an unsuitable tool or contacts poorly seated on the cable.
  • Connectors from different manufacturers mated together even though they appear compatible, which do not guarantee correct contact pressure.
  • Connectors not fully latched or subjected to mechanical strain from taut cables.
  • Ingress of water or dirt, which corrodes the contacts, and connectors resting on the roof instead of being secured.
  • Cable with a cross section or insulation unsuited to the current and the exposure.

How they are detected

Thermography with the system under load reveals connectors hotter than their neighbors. Discoloration, deformed plastic or burn marks may also be visible. Some inverters detect arcs and trip, which appears in the event logs as an arc fault. A string with lower voltage than expected may indicate a high-resistance connection.

What to do if you suspect a problem

Isolate the connector and replace it with compatible parts and the tool specified by the manufacturer; do not make an improvised repair. Checking the remaining joints from the same lot or the same installation prevents repeat failures.

Notice

Any work on an energized photovoltaic array, with DC voltages that are not interrupted by opening a disconnect switch on the AC side, must be carried out by qualified personnel in accordance with the applicable electrical safety regulations.