What is total demand distortion of current?

Total demand distortion of current, TDD, is the root of the sum of the squares of the harmonic currents expressed as a percentage of the maximum demand load current, not of the instantaneous fundamental current.

Definition

TDD quantifies how much harmonic current an installation contributes relative to its typical load capacity. It is calculated from the harmonic content of the current, excluding the fundamental, and divided by the maximum demand load current at fundamental frequency. The latter is taken as a fixed reference value, usually the average of the maximum demands over a representative period.

Difference from current THD

Current THD divides by the fundamental current measured at each instant. At light load, that fundamental is small, and even if the harmonic current is modest in amperes, the THD can be very high. That figure is alarming even though there is no real problem for the network, because few harmonic amperes are flowing. TDD avoids this effect by using a constant base.

Indicator Comparison base Behavior at light load
Current THD Instantaneous fundamental Can be very high
TDD Maximum demand current Low, because it reflects actual harmonic amperes

What it is used for

It is the indicator that recommendations such as IEEE 519 use to limit a user’s injection of harmonic currents at the point of common coupling. The permitted limits depend on the ratio between the short-circuit current available at that point and the demand current: a small installation on a strong network can tolerate a higher percentage. For specific values, consult the current edition of the applicable document.

How to interpret the result

  • It is evaluated at the point of coupling and not at each individual load, because that is where the contributions add up.
  • The reference demand current must be clearly defined; if the base changes, the value changes.
  • A high TDD indicates that nonlinear equipment is contributing significant harmonic current relative to the capacity of the installation. The cause is located by identifying the loads, for example drives or rectifiers without filtering.

What the engineer sees in practice

Analyzers report TDD as a percentage over time, along with the current. It is common to compare a high percentile of the recorded values with the limit, and not just the average, because the limit refers to sustained normal operating conditions.