What is spreading resistance?

It is the resistance the soil offers to the current flowing from the electrode toward remote earth; it is not the resistance of the electrode metal, but that of the volume of earth surrounding it.

Definition

Spreading resistance, or the ground resistance of an electrode, is the ratio between the potential the electrode acquires with respect to remote earth and the current it disperses into the soil. It is the resistance of the electrode-soil assembly, and almost all of its value is due to the soil.

Why it is concentrated near the electrode

Imagine the current leaving the electrode in all directions. Around it, each layer of soil behaves like a concentric shell. Near the electrode the cross section through which the current passes is small, so each layer contributes a great deal of resistance. As we move away, the cross section increases rapidly and the layers contribute less and less. In practice, most of the resistance lies in a relatively nearby volume of soil.

For this reason the electrode material matters little and the shape matters a great deal: a longer electrode, or one with more exposed area, offers the current more surface through which to leave.

What it depends on

  • Soil resistivity. It is proportional: twice the resistivity gives twice the resistance for the same geometry.
  • Electrode geometry. Length, diameter, configuration and depth.
  • Moisture, temperature and salts. They change the resistivity with the seasons.
  • Interference between electrodes. Several nearby electrodes share the same volume of soil and do not reduce the resistance in proportion to their number.

How it is measured

With the fall-of-potential method, which uses a current stake and a potential stake placed far enough from the electrode to be outside its zone of influence. There are also clamp methods for electrodes in parallel with others, which have limitations and assume a low-resistance return path.

A useful clarification

At power frequency a resistance is measured, but with lightning or high-frequency currents the electrode behaves as an impedance, with inductive and propagation effects. A low value at low frequency therefore does not ensure the same performance under transients. Measurements and work on energized electrical installations must be performed by qualified personnel, in accordance with applicable regulations and site safety procedures.