What is soil resistivity?

Soil resistivity is the opposition a volume of soil offers to the flow of current; it is expressed in ohm-meters and determines how much resistance a buried electrode will have.

Soil resistivity is a property of the material, not of an electrode. It describes how difficult it is for current to pass through a cube of soil and is expressed in ohm-meters. The higher it is, the more resistance the soil offers and the harder it is to obtain a good ground.

Why soil conducts

Dry minerals are almost insulators. Conduction in soil occurs mainly through the ions dissolved in the water that fills the pores. For this reason resistivity depends less on the rock and more on how much water is present and what salts it contains.

Factors that change it

  • Moisture: more water means lower resistivity, up to a certain limit.
  • Dissolved salts: they increase the number of ions and reduce resistivity.
  • Temperature: resistivity rises as temperature falls, and especially when the water freezes.
  • Composition and compaction: clays, sands, gravel and rock behave very differently.
  • Stratification: soil is usually made up of layers with different values.

What is seen in practice

Resistivity measured in the field is apparent: it averages the volume of soil the method explores. If the measuring electrodes are spaced farther apart, greater depth is explored. That is why the same area yields different curves depending on the spacing, and the layer model is inferred from them.

How to use it

In the design of a grounding system, resistivity is the input that determines the length of conductor and the number of electrodes required. With a wrong value, the calculation of resistance, potential rise, and step and touch voltages comes out wrong in the same proportion.

When to distrust a value

A single value taken in a single season, or near buried metal pipes, may not represent the soil. It is advisable to measure in several directions, record the soil conditions and take seasonal variation into account. Measurements must be made by trained personnel, avoiding areas with buried energized installations.