A practical definition
An ideal network delivers a sine wave of constant amplitude and frequency, balanced between phases. In practice, any deviation from that shape is a power quality problem, but it only matters when it affects a piece of equipment or a process. That is why quality is always evaluated as a pair: what the network delivers and what the load can withstand.
Why it happens
Disturbances arise in two places. Some come from the network: switching operations, remote faults, lightning. Others are generated by the installation itself: nonlinear loads such as drives and switch-mode power supplies, large motor starts, welders or arc furnaces. The source impedance turns the distorted load current into distorted voltage, which the other equipment then sees.
Families of disturbances
- Amplitude variations: voltage dips or sags, temporary overvoltages and interruptions.
- Waveform distortion: harmonics, interharmonics and DC component.
- Unbalance: differences in magnitude or angle between phases.
- Rapid fluctuations: flicker, perceptible in lighting.
- Transients: very brief impulses and oscillations.
- Frequency deviation.
What an engineer sees in the field
The symptoms rarely say “poor power quality.” They show up as random PLC restarts, drive trips on DC bus undervoltage, transformers or capacitors running hotter than expected, circuit breakers tripping with no apparent overload, or flickering lamps. A power quality analyzer records waveforms and time-stamped events, and it is the correlation between the event and the process shutdown that identifies the cause.
Common mistakes
- Measuring for a few minutes with an average-responding multimeter and concluding that the voltage is correct; brief events are missed.
- Measuring only at the service entrance when the problem originates inside the plant, or the other way around.
- Mistaking a voltage sag from the network for an internal fault without checking the direction of the event.
- Correcting power factor with capacitors without considering harmonics, which creates a risk of resonance.
- Comparing results without knowing the standard or criterion they are being evaluated against.
How to approach it
The sensible order is to define the symptom, record at the right point for a period representative of operations, identify the disturbance and its source, and only then decide among filters, reactors, circuit separation, backup power or a change in equipment specification. Measurements on energized panels are the responsibility of qualified personnel following the applicable electrical safety regulations.