The central idea
No insulation withstands every overvoltage, and protecting against all of them would be impractical. Insulation coordination seeks a balance: knowing the overvoltages that can appear on a network, defining the voltage level each piece of equipment must be able to withstand, and installing protective devices that limit those overvoltages to below that level, with a margin. The goal is a probability of failure that is acceptable in technical and economic terms.
The three related elements
- Stresses: the overvoltages that reach the equipment. They can be atmospheric in origin (lightning strikes on lines), switching-related (closing and opening of breakers) or temporary (from ground faults or load rejection).
- Protection: normally lightning arresters or surge arresters, which conduct the surge current to ground and limit the voltage at their terminals.
- Insulation withstand: the voltage the equipment withstands in standardized tests, which differs for fast impulses and for power-frequency voltage.
How the margin is reasoned
The voltage that actually reaches the equipment is not the voltage at the arrester terminals: it depends on the distance between the two, the inductance of the conductors and wave reflections. This is why the withstand voltage of the equipment is compared with the voltage limited by the protection plus a safety margin. The closer the arrester is to the equipment it protects, the more reliable the protection.
What an engineer sees in practice
On a project, coordination translates into concrete decisions: what insulation class transformers and switchgear will have, what insulation distances will be used in air, where arresters are installed and what characteristics they will have. In operation, repeated insulation failure with no apparent cause can indicate that the coordination fell short, for example after a network was expanded or a cable was replaced by another with a different impedance.
When coordination fails
- Arresters incorrectly sized for the system’s continuous operating voltage.
- Long connections between arresters and ground, which raise the residual voltage.
- Aging of the insulation, which reduces its actual withstand voltage compared with that of new equipment.
The coordination study must be done by qualified personnel and be based on the applicable standard, in its current edition.