What is inert gas asphyxiation?

Inert gas asphyxiation occurs when a non-toxic gas such as nitrogen, argon or helium displaces the oxygen in the air and a person is left without enough oxygen, with no odor, irritation or feeling of suffocation to warn them.

Inert does not mean harmless

An inert gas does not react and is not toxic, but in an enclosed space it can be deadly through displacement. Air is made up mainly of oxygen and nitrogen. If an inert gas is introduced, the proportion of oxygen drops because the available space is the same. The person breathes, but the air they breathe does not sustain life.

Why there is no warning

These gases have no odor or color and do not irritate. In addition, the urgent reflex to breathe is triggered mainly by carbon dioxide in the blood, not by a lack of oxygen. If the air being breathed lacks oxygen, the body does not send a strong alarm signal. The person may feel briefly dizzy and lose consciousness within moments. Anyone with them may not know what happened and may go in to help.

Where it occurs in industry

  • Nitrogen purging of tanks, piping and reactors, when the equipment is opened afterward.
  • Welding shielding gas, such as argon, which collects in pits, tanks or vessels.
  • Storage areas and cryogenic rooms where a cryogenic liquid evaporates and expands into a large volume of gas.
  • Extinguishers and gas suppression systems, whose discharge changes the atmosphere of the room.
  • Fermentation and carbon dioxide in cellars and cisterns.

How they distribute

Density relative to air determines where they concentrate. Argon and carbon dioxide are heavier and collect at the bottom, which explains accidents in pits and tanks. Nitrogen has a density similar to that of air and tends to mix; helium is lighter and rises. However, a cold gas, such as the gas coming off a cryogenic liquid, can behave like a heavy gas at first.

Carbon dioxide: a special case

Carbon dioxide does not just displace oxygen; at high concentrations it also has its own effects on breathing and consciousness. It is treated as both an asphyxiant and a toxic hazard.

How it is prevented

  1. Physically isolate equipment from inert gas lines, rather than just closing valves.
  2. Ventilate and confirm with an oxygen meter before entry, at several levels.
  3. Keep measuring continuously during the work.
  4. Have a rescue plan that does not involve unprotected people entering.

An oxygen detector is the only way to recognize this hazard. Entry and measurements must be carried out by trained, authorized people, in accordance with applicable regulations.

This guide is for information only. Work involving electrical hazards, heights or hazardous atmospheres must be carried out by qualified, authorized personnel in accordance with applicable regulations.