What is indirect electrocution by step voltage?

Indirect electrocution by step voltage occurs when a person touches no conductor, but their two feet are at points on the ground with different potentials because a fault current is dispersing into the earth.

The ground is not a single potential

When a ground fault injects current into the earth (a downed conductor, a fault in equipment connected to a grounding system, a lightning strike), that current disperses through the soil and meets resistance as it travels. As a result, the surface potential is not uniform: it is higher near the injection point and decreases with distance, forming a kind of gradient around it.

How the shock occurs

If a person walks through that zone, each foot is at a point with a different potential. The difference between the two is the step voltage. That difference drives current from one foot to the other through the body, without the person having touched anything energized. That is why it is called indirect.

Relationship with other voltages

  • Step voltage: the difference between two points on the ground separated by the distance of one step.
  • Touch voltage: the difference between a grounded metal structure and the ground where the feet rest, when that structure is touched.
  • Ground potential rise: the increase in the potential of an entire installation relative to remote earth during a fault.

What the risk depends on

  • The magnitude of the fault current and the time the protection takes to clear it.
  • Soil resistivity: a more resistive soil produces steeper gradients.
  • The design of the grounding system: a well-designed grid smooths the gradient at the surface.
  • High-resistivity surface layers, which increase the resistance in series with the body.
  • The distance between the feet: a long step increases the difference.

What is done to reduce it

In substation design, the aim is for the ground grid to keep step and touch voltages below tolerable limits, reinforced with a surface layer of resistive material. Protection that clears the fault quickly limits the exposure time.

What to do around a downed conductor

Assume that the nearby ground is energized. The usual recommendation is not to approach and, if you are inside the zone, to move away with very short steps or by hopping with your feet together, and to notify qualified personnel and the utility. Do not attempt to rescue anyone until the zone is confirmed to be safe.

Operations in these areas must be carried out by qualified personnel, following the applicable regulations.