24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What is high-frequency ground impedance?

High-frequency ground impedance is the opposition a grounding system presents to rapidly changing currents, such as those of lightning, and it differs from its resistance to low-frequency AC or to DC.

The ground resistance measured with an earth resistance tester describes the behavior of the system at low frequency. But a lightning discharge contains very high-frequency components, and at those frequencies the grounding system behaves differently. High-frequency ground impedance describes that response.

Why it changes

At low frequency, current spreads along the entire electrode and the behavior is practically resistive. At high frequency, two effects come into play:

  • Conductor inductance: its reactance grows with frequency and limits the current that can travel toward the farthest ends.
  • Capacitance to the soil and propagation: the electrode stops being a point and behaves like a lossy transmission line.

Effective length

A practical conclusion follows: a very long ground conductor stops being useful beyond a certain length, because impulse current dissipates near the injection point. Lengthening an electrode reduces low-frequency resistance, but it does not necessarily improve the impedance seen by lightning. It is more effective to spread the dissipation over several short radial conductors than over a single long one.

Effect of ionization

When current density in the soil is very high, the electric field can ionize the soil near the electrode and temporarily reduce its effective resistance. This phenomenon depends on current magnitude and soil resistivity, and it is taken into account in lightning study models.

What the engineer sees

A ground with a good low-frequency resistance value can still produce high overvoltages during a lightning strike: long connection cables or cables with tight bends add inductance that shows up as a voltage drop during the impulse. That is why down conductors and connection conductors are kept short and straight.

When conventional measurement is not enough

For lightning protection systems or installations with sensitive electronic equipment, low-frequency measurement is necessary but insufficient. It is advisable to complement it with design criteria from the current standard and, when required, with measurements using impulse currents performed by qualified personnel.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer