What is ground fault current and how is it limited?

Ground fault current is the current that flows to ground when an energized conductor loses its insulation, and its value is determined mainly by the impedance through which the system neutral is grounded.

What it is and what it depends on

A ground fault occurs when a live conductor makes contact with ground or with a grounded metal part. The resulting current depends on the phase voltage and the total impedance of the return path: the zero-sequence impedance of the source and wiring, the impedance of the fault point itself, and the impedance placed between neutral and ground. With the neutral solidly connected to ground, that current can be very high; with an impedance in the neutral, it is limited.

Why limiting it matters

  • A high current causes thermal and mechanical damage in the faulted equipment, for example in the laminations of motors and generators.
  • It intensifies the arc and the risk to people.
  • It causes deep voltage sags in the rest of the system.

But limiting it too much makes detection difficult. It is a trade-off.

Ways to limit it

  • Low-value resistance: allows enough current for sensitive protections to detect the fault and trip quickly, without reaching the magnitude of a solid fault.
  • High-value resistance: restricts the current to a very low level, such that the equipment can keep operating during the first fault while it is located. It requires detection and alarm, and design for transient overvoltages.
  • Reactance: reduces the current with lower heat losses, but can give rise to transient overvoltages if poorly chosen.
  • Isolated neutral: the current depends on the system’s capacitances to ground.

How it is detected

Ground overcurrent relays are used, fed by the sum of the three phases or by a current transformer that encircles the three conductors, known as a zero-sequence transformer. Their setting must take into account normal unbalance currents and the maximum current the limiting device allows.

What the engineer sees

Ground protection trips, localized damage to laminations or windings, heating of neutral resistors after an event and, in isolated systems, ground fault alarms that must be dealt with promptly. Grounding systems and the associated tests are work for qualified personnel.