Equipotential bonding, also simply called bonding, consists of electrically joining exposed metal parts, structures, pipes and other conductive parts so that they all take on practically the same potential. The goal is not to bring them to absolute zero, but to prevent a voltage difference from appearing between them that could harm a person or a piece of equipment.
The principle
The risk of electric shock depends on the potential difference between two points a person touches at the same time, not on the potential relative to a distant reference. A bird on an energized wire receives no shock because its feet are at the same potential. Equipotential bonding applies the same idea to an entire installation.
How it differs from grounding
Grounding fixes the potential reference of the assembly relative to the soil. Equipotential bonding ensures that the elements of the assembly move together. An installation can be well grounded and poorly bonded, for example a pipe that keeps a different potential from the enclosure of a nearby piece of equipment, and vice versa. The two measures complement each other.
Where it is applied
- Between equipment enclosures and nearby metal structures.
- On metal water, gas and process pipes entering a building.
- Between sections of cable tray, ducts and shielding.
- In areas at risk from static electricity or explosive atmospheres.
What is verified
The quality of a bond is evaluated by its continuity, that is, by the low resistance between the connected parts, measured with a low-resistance instrument at a suitable test current. A conductor without real continuity, because of paint, corrosion or a loose connector, does not do its job even if it is visible.
An example
Two panels fed from different points and connected by a shielded signal cable can have their enclosures at different potentials during a fault. If they are not bonded, that difference drives current through the shield and damages interfaces. With a low-impedance bond, the difference is reduced and current stops passing through the signal cable. Installations must be carried out by qualified personnel in accordance with the applicable regulations.