What Is Dielectric Absorption?

Dielectric absorption is the gradual increase in the polarization of an insulator when DC voltage is applied; it shows up as a current that decays over time and is used to judge whether the insulation is clean and dry.

What happens inside the insulator

When DC voltage is applied to insulation, the measured current is not constant. It has three components: a capacitive current, which disappears very quickly; an absorption current, which decays slowly as the charges in the material orient and accumulate; and a conduction or leakage current, which remains practically constant. Dielectric absorption is that slow polarization phenomenon.

How it shows up in the test

Insulation resistance, calculated as voltage over current, increases with time as the absorption current decreases. In clean, dry insulation, the increase is clear and sustained. In wet or contaminated insulation, leakage current dominates and the resistance hardly changes with time.

The indices

  • Dielectric absorption ratio: the quotient of the resistance at a long time and at a short time, for example the one-minute reading divided by the half-minute reading.
  • Polarization index: the quotient of the ten-minute reading and the one-minute reading.

Both indicate the slope of the resistance curve, not the absolute value. A value close to one suggests that leakage current dominates, and a higher value suggests healthy behavior. Acceptance criteria depend on the type of equipment, the insulation class and the applicable standard.

How to interpret the result

  1. Compare with earlier measurements on the same equipment under similar conditions.
  2. Correct for or record the temperature, which changes the resistance.
  3. Take the surface condition into account: dirt and moisture on terminals alter the reading.
  4. Combine with other tests, such as power factor or tan delta.

When the index is misleading

Very good insulation can give an index close to one if the absorption current is already minimal from the start, which is why some standards consider it uninformative when the resistance is very high. In modern insulation and some materials, the reading behaves differently than in older systems.

After the test

The insulation remains charged like a capacitor. It must be discharged to ground for a sufficient time, in proportion to the time it was under voltage, before it is touched or disconnected.

Warning: insulation tests involve hazardous voltage and stored energy. They must be performed by qualified personnel, in accordance with applicable regulations.