What is ATPV?

ATPV is the thermal energy value, expressed in calories per square centimeter, at which a material or garment has a 50% probability that the skin underneath will suffer a second-degree burn when exposed to a test electric arc.

Definition

ATPV stands for Arc Thermal Performance Value. It is a measure of the thermal performance of a fabric or garment system against an electric arc. It is expressed in cal/cm² and represents the incident energy at which there is a 50% probability that the heat transmitted through the material will cause a second-degree burn, according to a skin damage prediction criterion.

How it is obtained

In a laboratory, the textile sample is exposed to test electric arcs at different energy levels. Calorimetric sensors behind the sample record the transmitted heat. That record is compared with a skin tolerance curve. By repeating tests at different energies, the level at which the burn probability reaches that halfway mark is estimated.

The detail almost everyone overlooks

Some materials do not let enough heat through to reach the burn criterion, but they break or open up first. In that case another value is reported, the breakopen energy or EBT, instead of ATPV. In practice both are interpreted the same way: they are the garment’s arc rating. The label indicates which of the two applies.

How it is used

  1. Determine the expected incident energy at the work location, through an arc flash study or a recognized tabular method.
  2. Choose a garment or system with an arc rating equal to or greater than that energy.
  3. Verify that the value applies to the complete combination of layers, not to a single layer.

What ATPV does not tell you

  • It does not guarantee there will be no injuries: 50% is a probability, not an absolute safety boundary.
  • It does not cover the pressure, shrapnel or noise effects of the arc.
  • It does not apply to garments that are worn, contaminated with oils, washed in a way that damages the treatment, or poorly fitted.
  • It is not equivalent to the PPE category: the category is a grouped level; ATPV is the measured value of a material.

In practice

An engineer sees ATPV on the garment label or the manufacturer’s data sheet and compares it with the calculated incident energy. If the value is insufficient, the first step is to try to reduce the energy (shorter clearing time, a different configuration, de-energized work) before asking for a heavier garment. Selection and use of arc PPE must be done by qualified personnel, in accordance with the applicable regulations.