An isolated ground is an equipment grounding conductor that runs separately and with its own insulation, so that it does not touch the raceway, the box or the metal enclosure along its route. It connects to the ground terminal of a special receptacle or of a piece of equipment and returns to the grounding point at the origin of the installation.
What problem it tries to solve
In a normal installation, metal raceways and enclosures are part of the ground path, and small leakage, harmonic or noise currents from other equipment can flow through them. Sensitive electronic equipment connected to that "shared" ground can see that noise as interference in its reference. An isolated ground offers a cleaner reference path, with fewer stray currents flowing along it.
What it is not
- It is not an independent ground with no connection to the rest of the installation. It joins the system at one point, normally the origin.
- It does not replace the protective conductor of the raceway. Safety under fault conditions still depends on a low-impedance path, which is why an isolated ground is installed in addition to that path, not in place of it.
- It does not reduce noise entering by other routes, such as the phase or neutral conductor, or by radiated coupling.
When it is used
It is considered in installations with data processing equipment, instrumentation or control with a sensitive reference, when noise on the conventional protective conductor causes malfunctions. Before resorting to it, it is advisable to confirm that the problems do not come from loose connections, shared neutrals or multiple neutral-to-ground bonds.
When it does not apply
It is a limited measure. If there is an accidental bond between the insulated conductor and the raceway, the advantage disappears and a loop is created. If the equipment is interconnected with another that has its own reference, potential differences can appear between them. Any use must comply with the current electrical code and the equipment manufacturer’s instructions.
The installation and modification of grounding systems must be carried out by qualified personnel, in accordance with the applicable safety regulations.