What is an equipment voltage sag tolerance curve?

An equipment voltage sag tolerance curve is a graph of voltage magnitude against duration that marks out the zone in which a type of equipment usually operates without problems and the zones where it may fail, and it is used to assess the effect of recorded events.

What it represents

The horizontal axis is the duration of the event, normally on a logarithmic scale, and the vertical axis is the remaining voltage relative to nominal. The curve traces a boundary: above and below certain levels, for each duration, the equipment may lose function. Above the upper boundary there is also an overvoltage zone.

Well-known examples

The CBEMA curve and its successor, ITIC, were formulated for information technology equipment with single-phase power. There is also a curve for semiconductor manufacturing equipment. These are generic references, and each manufacturer may have a different tolerance.

How it is used

  1. Voltage events are recorded with their duration and depth.
  2. Each event is marked as a point on the plane.
  3. Points inside the acceptable operating region should not cause shutdowns; those outside it are candidates to explain failures.
  4. The number of events falling outside, and how often, is counted to size the problem.

How it supports decisions

The curve is used to compare the sensitivity of the process with the electrical environment. If many events fall outside, you can improve the equipment (adjust the undervoltage threshold of a drive, use backup power) or the power supply. Knowing the typical depth and duration of network sags helps in choosing the mitigation system.

Limitations

  • It is a generic curve; actual tolerance varies by model, load and operating state.
  • It sums up the event in two numbers and omits the phase angle jump, the point on the wave where it began and the unbalance between phases.
  • Three-phase and single-phase sags affect equipment differently.
  • The curves were conceived for low-voltage single-phase loads and cannot be applied without care to three-phase motors or processes.

What the engineer sees in practice

A graph with the curve and clouds of points for the events in the measurement period. The most useful conclusion is not to stop at pass or fail, but to test the tolerance of the specific critical equipment, for example with sag immunity tests, and build its own curve.