What Is an Acoustic Partial Discharge Detector?

An acoustic partial discharge detector uses piezoelectric sensors to pick up the sound waves produced by a partial discharge, making it possible to detect and locate defects without being affected by electrical noise.

What it detects

A partial discharge releases energy in a very small volume and generates a high-frequency mechanical wave that travels through the oil, the solid or the air. The acoustic detector picks up this wave with a sensor, amplifies it and presents it as a signal for analysis.

Components

  • Piezoelectric sensor: converts vibration into an electrical signal. It can be mounted in contact with the outer wall of a tank, or it can be an airborne ultrasonic sensor that picks up sound at a distance.
  • Preamplifier and filters: remove low-frequency noise, such as equipment hum.
  • Recorder or analysis instrument: displays the pulses and their relationship to the phase of the applied voltage.

How the defect is located

If several sensors are placed at different points, each one receives the pulse at a different instant. From the speed of sound in the medium and the time differences, the position of the source is calculated, in a way similar to triangulation. In transformers this is used to locate the origin inside the tank.

Advantages and limits

  • Immunity to electrical noise: useful in the field, where interference makes electrical measurement difficult.
  • Measurement without electrical contact with the circuit: it can be performed with the equipment in service.
  • No calibration in picocoulombs: the acoustic signal does not relate reliably to apparent charge, so it does not quantify severity by the same criterion as the electrical method.
  • Attenuation: the signal weakens and is reflected by internal structures, so a deep defect may not be picked up.

How to interpret the result

Acoustic detection confirms the presence and approximate location of a source, and is used together with the electrical method to evaluate its severity.

These activities involve hazardous voltages: they must be carried out by qualified, authorized personnel, following the applicable regulations and the facility’s lockout and grounding procedures.