What it is
A phasor represents a sinusoidal signal by its magnitude and phase angle. The angle only makes sense against a reference. A synchrophasor ties that reference to a common absolute time scale: the angle is calculated with respect to a cosine wave whose phase is locked to Coordinated Universal Time. Phasors measured at distant locations can therefore be compared directly.
What measures it
The phasor measurement unit (PMU) samples voltages and currents, calculates the phasor of the fundamental and assigns it a precise time stamp taken from an external source, usually a satellite receiver. It also estimates frequency and its rate of change. It sends the results several times per second, at a rate tied to the grid frequency, to data concentrators that align the streams from different PMUs by their time stamps. The format and performance requirements are covered in the IEEE C37.118 standard, whose current edition should be consulted.
What it makes possible
- Seeing angle differences between distant points on the grid, which indicate line loading and stability margin.
- Detecting electromechanical oscillations between areas.
- Analyzing disturbances with a simultaneous view of several nodes.
- Validating models and estimating the system state more directly.
What limits accuracy
Time error translates into angle error, proportional to frequency: the more precise the clock, the smaller the phase error. Instrument transformers and wiring also have an influence, since they introduce magnitude and angle errors, as does the presence of harmonics and transients in the signal.
How it differs from a conventional meter
A common analyzer records RMS values and averages using its own clock. A PMU delivers phasors at a high reporting rate, synchronized between locations. It does not replace a power quality analyzer, because its aims are the dynamic state of the system, not distortion or waveform events.