What it is for
A conventional current transformer (CT) is installed in series with the conductor, which requires disconnecting it. A split-core, or open-core, CT has a magnetic core in two halves that separates to surround the conductor and then closes. This makes it possible to install a current measurement, for example for an energy meter or an analyzer, without interrupting service.
How it works
The conductor passing through the center is the primary winding, with a single turn. The primary current creates a flux in the core that induces a proportional current in the secondary winding, according to the transformation ratio. That current (or a voltage, in models with an internal burden resistor) is sent to the instrument.
What affects accuracy
- Air gap at the joint: the core faces must mate perfectly. Dirt, rust or misalignment increase the reluctance and produce ratio and phase-angle errors.
- Burden: the impedance connected to the secondary, including the wiring, must be within what the transformer can handle in order to maintain its accuracy class.
- Saturation: large currents or DC components can saturate the core and distort the signal.
- Conductor position and neighboring conductors, which have a small influence.
Secondary circuit precaution
A current-output CT must not operate with the secondary open while current flows through the primary: the voltage that appears can be dangerous and can damage the insulation and the core. Voltage-output models already include an internal burden, but they must not be modified without knowing the manufacturer’s instructions.
Common mistakes
- Orienting the arrow incorrectly and getting powers with reversed sign.
- Choosing a range too large for the actual current, losing accuracy at the low end.
- Closing the core with dirt present or without checking that it closes completely.
- Using them to measure direct current, for which they are of no use.
Installation on energized conductors is work for qualified personnel, in accordance with applicable safety regulations.