24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

What is a short-circuit study?

A short-circuit study calculates the currents that would flow through each point of an installation during a fault, to confirm that equipment and protections can withstand and interrupt those currents.

What it calculates

A short-circuit study estimates, at each bus and panel, the current that would flow if a fault occurred at that point. Different fault types are calculated: three-phase, phase-to-phase, phase-to-ground, and double phase-to-ground. The three-phase fault usually gives the highest current at many points, but the phase-to-ground fault may be the highest at some, for example near certain transformers or generators, and it is essential for ground protections.

Where the current comes from

  • The utility system, represented by its short-circuit power or impedance at the connection point.
  • Local generators.
  • Induction and synchronous motors, which behave as sources during the first cycles because their inertia keeps them turning and excited.
  • Inverters, with a contribution limited by their electronics.

The current is limited by the impedances of transformers, cables, and reactors between the source and the fault.

X/R ratio and asymmetry

The ratio of circuit reactance to resistance determines how far the current wave is displaced in the first instant, that is, the decaying DC component. A high X/R ratio produces a higher peak value and places greater demands on circuit breakers. That is why results are reported as symmetrical current and as an asymmetrical or peak value.

Scenarios

Maximum current cases are calculated, which size the interrupting capacity and mechanical strength of buses and equipment, as well as minimum current cases, which verify that protections still detect remote or low-contribution faults.

How the results are used

  1. Confirm that the interrupting capacity of each breaker and fuse exceeds the available current.
  2. Verify the withstand capability of buses, cables, and panels against thermal and mechanical stresses.
  3. Set the protection settings.
  4. Provide input for arc-flash incident energy studies.

The input data must be up to date with the actual installation. Methods and criteria are taken from the applicable standards in their current edition. All work on power equipment must be performed by qualified personnel.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer